Concrete masonry is a preferred material for use in constructing fire-resistive walls. It is a multi-functional system in a single package:
Noncombustible, stable in response to fire
Structurally sound, exceptional seismic performance
No toxic gases released when heated
Durable, long-lasting, with low life-cycle costs
The fire-resistance ratings of the various thicknesses of concrete masonry walls are based on 2019 CBC Table 721.1(2), Rated Fire-resistance Periods for Various Walls and Partitions, Item Numbers 3-1.1 through 3-1.4:
3-1.1 Expanded slag or pumice
3-1.2 Expanded clay, shale or slate
3-1.3 Limestone, cinders or air-cooled slag
3-1.4 Calcareous or siliceous gravel
Partial Grouted | Solid Grouted1 | ||||||
---|---|---|---|---|---|---|---|
CMU ASTM C90 Wt. Classification | NW | MW | LW | NW | MW | LW | |
Nominal Width |
4 | <1 Hour | <1 Hour | 1 Hour |
1 Hour |
1 Hour |
1 Hour |
6 | 1 Hour |
1 Hour |
1 Hour |
3 Hours |
3 Hours |
3 - 4 Hours2 |
|
8 | 1 Hour |
1 Hour |
2 Hours |
4 Hours |
4 Hours |
4 Hours |
|
10 | 2 Hours |
2 Hours |
2 Hours |
4 Hours |
4 Hours |
4 Hours |
|
12 | 2 Hours |
2 Hours |
2 - 3 Hours2 |
4 Hours |
4 Hours |
4 Hours |
|
1 4-inch wide cmu are solid units in lieu of solid grouted. |
Equivalent thicknesses are defined in 2019 CBC Section 722.3.1.
For partially grouted concrete masonry walls using 8-inch thick cmu rated at 2 hours, the fire-resistance rating can be increased to 4 hours when ungrouted cores are filled with any of the following:
Silicone-treated perlite loose-fill insulation conforming to ASTM C 549.
Vermiculite loose-fill insulation conforming to ASTM C 516.
Expanded clay, shale, or slate lightweight aggregate conforming to ASTM C 331.
Sand of slag having a maximum particle size of 3/8 inch, and conforming to ASTM C 33.
The calculated equivalent thickness of a concrete masonry wall may include the thickness of applied plaster and lath, gypsum wallboard, or gypsum plaster.
The fire-resistance rating of walls with cmu using blended aggregates is determined per 2019 CBC Section 722.3.1 and ACI 216.1/TMS 0216 [upon which Section 722.3.1 is based].
Download the Masonry Fire-Resistance-Rated Construction Code References. The document highlights code sections related to masonry and fire-resistance.